12.4 Priority Manager Conguration
Each zone microphone, reman microphone or audio input available in the system must have its priority dened in order to ensure
correct operation, as intended for sound emergency systems.
21.
1
Message priority mode in case of conict – FIFO / LIFO
Priority Resolve Mode this is a global system function which denes the system’s behaviour in case a conict occurs.
Theconict being a simultaneous transmission to the speaker zone from two or more audio sources of the same priority.
For FIFO (First in rst out) in the case when Source 1 of Priority X is transmitting to Output Y and after some time Source 2
of Priority X wants to transmit to Output Y too, Source 2 can not transmit until Source 1 has nished transmitting to Output Y.
For LIFO (Last in rst out) in the case when Source 1 of Priority X is transmitting on Output Y (speaker zone) and, after some
time, Source 2 of Priority X will start transmitting on Output Y (speaker zone) too, then Source 2 will replace Source 1, as
transmitting, and will commence transmitting to Output Y.
Priority Resolve Mode also determines the method of dynamic assignment of a backup power amplier in case a failure
occurs of the amplier modules which are responsible for transmission of simultaneous messages of the same priorities.
Incase two equally prioritized messages are executed to various zones, Message 1 of Priority (100), Message 2 of Priority (100)
too, which was matriced after Message 1 – when an amplier module failure occurs for the FIFO mode: the amplier which
supplies Message 1 will not be taken over by Message 2 until Message 1 (matrix) has been completed; for LIFO – theMessage
1 amplier module will be disconnected and assigned as a backup amplier for Message 2.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroVoice miniVES Series and is the answer not in the manual?

Autronica AutroVoice miniVES Series Specifications

General IconGeneral
BrandAutronica
ModelAutroVoice miniVES Series
CategorySecurity System
LanguageEnglish

Related product manuals