Electrical Noise Problems
Most noise problems result from improper grounding of the system. A good earth ground can
be the single most effective way to correct noise problems. If a ground is not available, install a
ground rod as close to the system as possible. Ensure all ground wires are single point grounds
and are not daisy chained from one device to another. Ground metal enclosures around the
system. A loose wire can act as a large antenna, introducing noise into the system. Therefore,
tighten all connections in your system. Loose ground wires are more susceptible to noise than
the other wires in your system. Review Chapter 4: Installation & Wiring if you have questions
regarding how to ground the touch panel.
Electrical noise can enter the system through the power source for the touch panel. Installing a
properly wired isolation transformer (neutral grounded) for all AC sources can help the
problem, but only if wired correctly. DC sources should be well-grounded good quality
supplies.
Never run communication cables or low-voltage power wiring close to high voltage wiring or
pulse generating wiring that controls such devices as solenoids, servos, VFOs, etc.
Selecting a lower communication rate in Panel Manager may help the panel resist noise.
8–10
Chapter 8: Troubleshooting
®
8
EA1-MG6-USER-M Hardware User Manual, 1st Ed. Rev C, 09/10

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the C-more micro EA1-S6ML and is the answer not in the manual?

C-more micro EA1-S6ML Specifications

General IconGeneral
BrandC-more micro
ModelEA1-S6ML
CategoryGraphics Tablet
LanguageEnglish