Reference from terminals 68 and 69.
Parameter 3-18 Relative Scaling Reference Resource
Table 202: Parameter 3-18 Relative Scaling Reference Resource
3-18 Relative Scaling Reference Resource
Default value: [0] No Function
Change during operation: True
N O T I C E
This parameter cannot be adjusted while the motor is running.
N O T I C E
The options [3],[4],[5], [6], [12], [13], and [14] are only available with software version 48.XX.
Select a variable value to be added to the fixed value (defined in parameter 3-14 Preset Relative Reference). The sum of the fixed and
variable values (labeled Y in Illustration 50) is multiplied by the actual reference (labeled X in Illustration 50). This product is then
added to the actual reference (X+X*Y/100) to give the resulting actual reference.
Relative
Z=X+X*Y/100
Resulting
actual
reference
Y
X
e30ba059.13
Z
Illustration 50: Resulting Actual Reference
AU275636650261en-000101 / 130R0334134 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide