Particulate and gaseous contamination specications
Table 18. Particulate contamination specications
Particulate contamination Specications
Air ltration Data center air ltration as dened by ISO
Class 8 per ISO 14644-1 with a 95% upper
condence limit.
NOTE: This condition applies only to data center environments. Air ltration requirements do not apply to IT equipment
designed to be used outside a data center, in environments such as an oce or factory oor.
NOTE: Air entering the data center must have MERV11 or MERV13 ltration.
Conductive dust Air must be free of conductive dust, zinc
whiskers, or other conductive particles.
NOTE: This condition applies to data center and non-data center environments.
Corrosive dust Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE: This condition applies to data center and non-data center environments.
Table 19. Gaseous contamination specications
Gaseous contamination Specications
Copper coupon corrosion rate <300 Å/month per Class G1 as dened by ANSI/ISA71.04-1985.
Silver coupon corrosion rate <200 Å/month as dened by AHSRAE TC9.9.
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Standard operating temperature specications
NOTE
:
1 Not available: Indicates that the conguration is not oered by Dell EMC.
2 Not supported: Indicates that the conguration is not thermally supported.
NOTE: All components including the DIMMs, communication cards, M.2 SATA, and PERC cards can be supported with sucient
thermal margin if the ambient temperature is equal to or below to the maximum continuous operating temperature listed in these
tables with the exception of the Mellanox DP LP card.
Technical specications 21

Table of Contents

Other manuals for Dell EMC PowerEdge C6420

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dell EMC PowerEdge C6420 and is the answer not in the manual?

Dell EMC PowerEdge C6420 Specifications

General IconGeneral
ProcessorIntel Xeon Scalable processors
ManagementiDRAC9
Max Processors2 per node
MemoryDDR4
StorageUp to 6 x 2.5" drives
Drive Bays24 x 2.5" or 12 x 3.5"
Network2 x 10GbE ports per sled
Power SupplyDual, 2000W
Operating System SupportWindows Server, Red Hat Enterprise Linux, SUSE Linux Enterprise Server, VMware ESXi
Maximum RAMUp to 3TB per node
Max MemoryUp to 3TB per node

Related product manuals