Chapter 2 Specifications and System Configuration
2-76
2_
AS-FPFN02
With its own standalone communication port, the extension card can work independently and can be set as a
PROFINET slave to connect to PROFINET network and exchange data with PROFINET master. After
installing the extension card, go to the PROFINET Configurator to set up the communication and download
the configurations to the master and then the master sends the configurations to the function card.
Wiring example
Linear Topology
2.10.2 Extension Card Profiles
AS-F2AD/AS-F2DA/AS-F422/AS-F485
37
23.9
59.3
60.8
1 5
Unit: mm
Pin no. AS-F2AD AS-F2DA AS-F422 AS-F485
1
V1+
VO1
R+
-
2
I1+
IO1
R-
-
3
V2+
VO2
T+
D+
4
I2+
IO2
T-
D-
5
COM
COM
SG
SG