DVP-ES3 Series Operation Manual
12-6
_12
12.2.3
ERROR LED Indicators Blinking Rapidly Every 0.2 Seconds
This happens when the power supply 24 VDC of the CPU module is disconnected, or the power supply is not sufficient,
not stable or abnormal.
Error
Code
(16#)
Description Solution Flag Log
002A The external voltage is abnormal.
Check whether the external 24 V power supply to the
module is normal.
SM7 V
12.2.4
ERROR LED Indicators Slow Blinking Every 3 Seconds and
Lighting up for 1 Second
Error
Code
(16#)
Description Solution Flag Log
1900
-
191C
Heartbeat errors occurred in the
slave for the Delta ASD-A2 control.
1. Check the CANopen connection cable.
2. Check if the specific slave is working properly.
Note: The last 2 digits of the error code represent the ID
number of the slave (convert hexadecimal to decimal).
- V
12.2.5
The LED RUN and ERROR Indicators are Blinking Simultaneously
Every 0.5 Seconds
This happens when the firmware of the CPU module is being upgraded. If this happens once the power is supplied to the
CPU module, it means errors occurred during the previous firmware upgrade. Users need to upgrade the firmware again
or contact your point of purchase.
12.2.6
The RUN and LED Indicators are Blinking One After Another Every
0.5 Seconds.
This happens when the CPU module memory card is backing up, restoring, or saving.
12.2.7
Other Errors (Without LED Indicators)
Error
Code
(16#)
Description Solution Flag Log
0011
The PLC ID is incorrect.
Check the PLC ID.
SM34
V
0012
The PLC password is incorrect.
Check the PLC password.
SM34
V
002D
The PLC maximum password attempts
exceeded.
Reset the CPU module or restore the CPU module
to its factory settings.
SM34 V
0050
The memories in the latched special
auxiliary relays are abnormal.
1. Reset the CPU module or restore the CPU
module to its factory settings, and then download
the program and the parameters again.
2. If the error still occurs, contact the factory.
SM6 V
0051
The latched special data registers are
abnormal.
1. Reset the CPU module or restore the CPU
module to its factory settings, and then download
the program and the parameters again.
SM6 V