AVERTISSEMENT: RISQUE D’EXPLOSION- NE PAS CONNECTER OU DECONNECTER TANT
QUE LES CIRCUITS SONT SUR TENSION SEULEMENT SI LA ZONE EST CONNU POUR ÉTRE
NON DANGEREUX
• WARNING: DO NOT USE USB PORT UNLESS THE AREA IS KNOWN TO BE NON-
HAZARDOUS
AVERTISSEMENT: NE PAS UTILISER PORT USB SEULEMENT SI LA ZONE EST CONNU
POUR ÉTRE NON DANGEREUX
• WARNING: EXPLOSION HAZARD. DO NOT REMOVE OR REPLACE CHARM MODULES
UNLESS POWER HAS BEEN DISCONNECTED OR THE AREA IS FREE OF IGNITIBLE
CONCENTRATIONS
AVERTISSEMENT: RISQUE D’EXPLOSION. NE PAS ENLEVER OU REMPLACER LES
MODULES DE CHARME À MOINS QUE L'ALIMENTATION SOIT DÉCONNECTÉE OU QUE
LA ZONE SOIT EXEMPT DE CONCENTRATIONS IGNITIBLES
• WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY
AVERTISSEMENT: LA SUBSTITUTION DE COMPOSANTS PEUT COMPROMETTRE LA
SECURITE INTRINSEQUE
• WARNING: DO NOT OPEN ENCLOSURE IN A DUST HAZARDOUS AREA
AVERTISSEMENT: NE PAS OUVRIR DANS UNE ZONE À RISQUE D’EXPLOSION DE
POUSSIÈRES
7.4 Technical data, explosion protection
The AMS Asset Monitor is checked and certified for the following, if connected to SELV/
PELV – electrical circuits for use in potentially explosive atmospheres:
IECEx/ATEX/CSA
Type of protection non-sparking nA in combination with nC
and [ic], depending on the installed
CHARMs
Identification IECEx/ATEX II 3G Ex ec nA nC [ic] IIC T4 Gc
III 2D Ex tb [ic] IIIC T75°C Db
CSA Class I, Zone 2 Ex/AEx ec nA nC [ic] IIC T4
Gc
Class I, Div 2 Group A, B, C, D T4
Zone 22 Ex/AEx tc [ic] IIIC T75°C Dc
Class II, Div 2 Group F, G T75°C
Class III
Temperature range -40°C < Tamb < 55°C
Standards IECEx IEC 60079-0:2017; Edition 7.0
IEC 60079-7:2017; Edition 5.1
IEC 60079-11:2011; Edition 6.0
IEC 60079-15:2010; Edition 4.0
IEC 60079-31:2013; Edition 2.0
Hazardous location installation Installation Guide
March 2024 MHM-97923-PBF
74 MHM-97923-PBF, Rev. 2.10