October 2019
Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
96
Section 12: Troubleshooting
Troubleshooting
12.4 The Motor is Very Hot and does not Start
Check that no alarm other than motor overheating is present.
Wait until the motor cools down and the normally closed (NC) contact of the
thermal switch automatically resets before trying to operate the actuator again.
Check that the number of operations per hour and their duration is suitable for the
actuator service (refer to the nameplate menu).
Check that the valve operating torque is within the range of the unit’s designed
operating torque.
Always check for causes of abnormal operation.
12.5 The Motor Runs but the Actuator does not
Move the Valve
If the valve position indicators do not change on the local display:
Check that the manual de-clutch lever is not stuck in the manual operation position.
Rotate the handwheel a few degrees to remove any possible sticking between the
handwheel and the drive sleeve.
Figure 83
Figure 84

Table of Contents

Other manuals for Emerson Bettis XTE3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Bettis XTE3000 and is the answer not in the manual?

Emerson Bettis XTE3000 Specifications

General IconGeneral
BrandEmerson
ModelBettis XTE3000
CategoryController
LanguageEnglish

Related product manuals