EasyManuals Logo
Home>Emerson>Controller>Bettis XTE3000

Emerson Bettis XTE3000 User Manual

Emerson Bettis XTE3000
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
67
Section 9: Set-Up Routines
Set-Up Routines
9.1.13 Miscellaneous
This includes different types of routines such as “time and date”, “lithium battery”, and
"torque prole", used only for special applications or in particular conditions.
9.1.13.1 Time and Date
Time and date are used in maintenance functions to associate time information to the
memorized event (torque prole, alarm log, maintenance request, etc.). Time and date
are entered at the time of manufacture, but they can be adjusted during commissioning or
maintenance operations.
Configuration procedure
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions (see
“Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
through the list of available routines, and then press YES to select "Miscellaneous".
Press YES to enter the time and date routine.
Press YES if the time is correct; otherwise, press NO to change it.
Enter hours, minutes and seconds. Press NO to scroll the list of available values,
and press YES to select.
Press YES when the time is correct.
Press YES if the date is correct; otherwise, press NO to change.
Enter day, month, and year. Press NO to scroll the list of available values, and YES
to select.
Press YES if the date is correct.
9.1.13.2 Torque Limits
Torque limits are used as a reference for the torque alarm and end of travel. With the
option “standard”, the torque limits are constant along the full stroke. The limits can be
congured in the “stroke limits” or “torque set-up” routines and can determine the torque
alarm or end of travel situations. In the same application it is useful to congure 3 different
torque thresholds for each traveling direction, to limit separately the unseating, running,
and ending torque. To select this option, pick “3-point limits” and then follow the torque
set-up and stroke limits routines (see Figure 64).
Configuration procedure
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions (see
“Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
through the list of available routines, and then press YES to select "Miscellaneous".
Press NO and then NO to select “torque mode”. Press YES if setting is correct;
otherwise, press NO to change. Press YES when the value is correct.
Repeat the stroke limits setting routine.

Table of Contents

Other manuals for Emerson Bettis XTE3000