Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
47
Section 6: Local Controls
Local Controls
6.4 Entering the Set-Up Mode
To change the existing settings or to set stroke limits it is necessary to enter the
correct password.
Ensure that mains power (or the external auxiliary supply) is supplied.
Move the 3-position selector to OFF and then simultaneously press OPEN/YES and STOP.
The display shows the present language. Press YES to conrm or NO to scroll
through the list of available languages. Press YES to select. Press YES to conrm
the chosen language.
Press NO when the message is “VIEW MODE OK?”. Press YES to answer the prompt
“ENTER PASSWORD OK?”.
Enter the password. Enter one digit at a time. Press YES if a digit is correct;
otherwise, press NO to scroll through the list of available characters and then press
YES when the character is correct. Enter 4 digits. After entering the last digit, the
microprocessor checks the password. If it is correct the messages “PASSWORD
CORRECT” and then “SET-UP MODE OK?” appear. Press YES.
Press NO to scroll through the list of available menus (actuator set-up, valve data,
maintenance) and press YES to select the desired menu.
Press NO to scroll through the list of available routines and press YES to select the
routine where the parameter to be changed is located.
Press YES and NO to answer the prompt on the display and change the parameter.
If the password is wrong, the message “PASSWORD WRONG” appears and set-up
mode will not available.
All settings are automatically saved to a non-volatile memory and are retained if electrical
power is removed from the actuator.
All XTE3000 actuators are congured before shipping with a standard default setting
unless alternatives were requested on order. If complications arise during commissioning,
the default setting can be reinstated via the appropriate function in the ”miscellaneous
routine in the actuator set-up menu. The actuator will return to its original conguration
and commissioning can resume.
6.5 Exit from View and Set-Up Mode
The following actions cause the actuator to exit from view and set-up mode:
Moving the 3-position selector to LOCAL or REMOTE.
Answering YES when the display asks “EXIT OK?”.
Pressing YES and NO simultaneously.
Automatic exit after 90 minutes without any parameter change or view.
Removal of electrical power from the unit.
Figure 54 shows the procedure to enter view and set-up mode.

Table of Contents

Other manuals for Emerson Bettis XTE3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Bettis XTE3000 and is the answer not in the manual?

Emerson Bettis XTE3000 Specifications

General IconGeneral
BrandEmerson
ModelBettis XTE3000
CategoryController
LanguageEnglish

Related product manuals