Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
79
Section 10: View Routines
View Routines
10.4.2 Torque Prole
The torque prole routine gives important information on the actuator working conditions
in comparison with a previously memorized reference prole. The torque prole can
indicate a change in process conditions.
Reference details are retained and the latest torque is expressed as a % of the nominal torque.
At the end of a full stroke in opening or closing, the XTE3000 stores the 3 maximum torque
values in position intervals 0%-10%, 10%-90%, 90%-100% in opening, and the 3 maximum
torque values in position intervals 100%-90%, 90%-10%, 10%-0% in closing. Time and date
of valve strokes are also saved. The above data are updated at the end of every full valve
stroke and the previous data are overwritten. The “set torque reference" function in the
SET-UP MENU, Maintenance, (Section 7), allows saving of the “torque prole” data in the
“torque prole reference” with a date and time. The “torque prole reference” will not be
updated until a new “set torque reference” command is entered. The user can compare the
last torque prole relevant to the last valve stroke with the torque prole reference saved
before.
The following denitions will be used:
Breakout: maximum torque % in position interval 0-10% in opening or 100%-90%
in closing = max. % of torque to unseat the valve.
Peak running: maximum torque % in position interval 10-90% in opening or
90% - 10% in closing = max. % of torque when the valve runs from Breakout to
Ending (maximum mid-travel).
Ending: maximum torque % in position interval 90-100% in opening or 10%-0% in
closing = max. % of torque to seat the valve.
The following data may be viewed:
Closing torque
Breakout %
Breakout reference %
Peak run %
Peak run reference %
Ending %
Ending reference %
Date of the last stroke
Date of reference (same of opening)
Opening torque
Breakout %
Breakout reference %
Peak run %
Peak run reference %
Ending %
Ending reference %
Date of the last stroke
Date of reference (same of closing)

Table of Contents

Other manuals for Emerson Bettis XTE3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Bettis XTE3000 and is the answer not in the manual?

Emerson Bettis XTE3000 Specifications

General IconGeneral
BrandEmerson
ModelBettis XTE3000
CategoryController
LanguageEnglish

Related product manuals