Section 9: Set-Up Routines
Set-Up Routines
9.3.4 Set Curve Reference
The “set curve reference” routine allows selection of 1 of 100 opening and closing torque
curves in the memory of the XTE3000 and to transfer them to the torque curve reference
registers. The old reference data are lost and the new data will become the new torque
curves' reference (see VIEW mode, Maintenance, Torque curve, Section 10.4.3).
Configuration procedure
• Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press NO to scroll through the list of available menus and then
press YES to select the "Maintenance" menu.
• Press NO to scroll the list of available routines and then press YES to select
"Set Curve Reference".
• Press NO to scroll the list and then press YES to select the desired curves (in
opening and closing).
• Press YES to update the torque curve reference.
9.3.5 Clear Recent Data Log
The clear recent data log routine allows the user to clear the counters of the recent
operation log. This command does not affect the content of the “general operation log”.
The date of the “clear recent data log” is memorized and can be viewed in the maintenance
date routine of the "View" menu.
Clearing procedure
• Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press NO to scroll through the list of available menus and press
YES to select the "Maintenance" menu.
• Press NO to scroll through the list of available routines and then press YES to select
"Clear Recent Data Log".
• Press YES.
• Press YES to clear or press NO to exit.