NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012 119
Drill Mode Special Zone Outputs
TM-4 polarity reversal alarm output
TM-4 municipal box output
UDACT/UDACT-2
Positive Alarm Sequence (PAS)
Outputs selected for PAS delay for 15 seconds. Acknowledgement within the 15-second delay will
set the Presignal Delay Timer to the full programmed value (60-180 seconds, including the PAS
delay of 15 seconds). When an alarm comes from an initiating device with a CBE list that includes
ZF0, the control panel delays the following outputs:
System Alarm relay
TM-4 polarity reversal alarm output
TM-4 municipal box output
UDACT/UDACT-2
C.2 Drill Mode
C.2.1 What is Drill Mode?
Drill Mode is a feature that customizes drill activations, allowing only specific devices on the
NFS2-3030 to activate when a local or network Drill is performed. These devices require the drill
zone (Special Function Zone 16) to be added to the zone mapping of each point. Refer to “Point
Program” on page 43.
There are two options for Drill Mode Programming:
Standard - The fi
re panel will turn on all appropriate output devices.
Custom - The fire p
anel will turn on all output devices with zone mapping that includes
Special Function Zone 16.
When in Standard Drill Mode:
The Drill Zone does not activate.
Performing a Signal Silence will turn off
all silenceable outputs.
Activation of another drill will return all silenceable outputs to an
active state.
All silenceable and non-silenceable outputs will turn off
following a System Reset.
When in Custom Drill Mode:
Performing a Signal Silence will turn off
all silenceable outputs.
Activation of second drill will not return the silenceable outputs to an active
state unless a
System Reset is performed.
All silenceable and non-silenceable outputs will turn off
following a System Reset.
The Drill Zone will remain active until a System
Reset is performed to clear the Drill
Condition.
The Drill Zone will activate when a drill is initiate
d from the fire panel keypad, ACS, a module set
as a drill switch, or via the network.