EasyManuals Logo
Home>Honeywell>Control Panel>nfs2-3030

Honeywell nfs2-3030 User Manual

Honeywell nfs2-3030
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #66 background imageLoading...
Page #66 background image
66 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Program Autoprogram Menu
Figure 3.56 Delete Point Screen
POINT SELECT: Press to scro
ll through the options: detector or module. Stop at the desired
option. Press the DELETE soft key to delete the point from programming. A confirmation screen
will display asking the user to confirm the deletion command.
NEXT/PREVIOUS SELECTION Press to
scroll sequentially to the next or previous point.
3.6 Autoprogram Menu
The Autoprogram option identifies addressable devices connected to the control panel. Devices
include addressable detectors and modules connected to the panel’s SLCs. The Autoprogram can be
used to create a new program, or to add or remove devices from an existing program. When the
points are accepted, they are added to the panel’s database with the defaults described in the “Point
Programming” section of this manual.
3.6.1 To Create a New Program
To successfully create a new program, the FACP must either be new, or have no existing program in
memory for the loops involved.
1. Use the Delete Program Menu screen (refer to Figure 3.55) to clear any applicable
programming from the panel. For example, if loops on
e and two are to be autoprogrammed,
clear the programming that exists by entering 1+2 at the Delete Program Menu screen.
2. Install SLCs (loops 1+2 in this
example) using the Loop Programming screen (Figure 3.27).
3. Press the
AUTOPROGRAM LOOPS soft key and enter the desired SLCs (loops 1+2 in this
example) in the Autoprogram Menu screen (Figure 3.57)
4. Press the ACCEP
T soft key to run the Autoprogram.
3.6.2 To Add/Delete Devices from the Program
When using the Autoprogram option with an existing program, the control panel does not change
program information for installed and programmed devices.
1. If devices are to be added to a new SLC (an SLC that is
not in the program), that SLC must be
installed using the Loop Programming screen (Figure 3.27).
DELETE POINT
POINT SELECT:
LyyDzzz (DETECTOR)
NEXT SELECTION DELETE
PREVIOUS SELECTION BACK
NOTE: Deleting points that are active or in trouble will cause a reboot.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell nfs2-3030 and is the answer not in the manual?

Honeywell nfs2-3030 Specifications

General IconGeneral
BrandHoneywell
Modelnfs2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals