84 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Alter Status Control On/Off Point Select
Soft Keys
POINT: Press this soft key to enter the point address or
general zone number (except Z000) to be
forced on or off.
NEXT/PREVIOUS SEL
ECT
ION: Press to progress to the next or previous point on the loop, or
the next or previous general zone.
ACCEPT: Press to
continue to the Control On or Control Off screen.
4.8.1 Control Off
One of the following two screens will display when a point or general zone is selected and accepted
in the previous screen.
If the selected point or zone is active, the Control Off screen will appear.
Figure 4.17 Control Off Screen
Soft Keys
FORCE OFF: Press this
soft key to change the state of the control module or general zone from
AUTOMATIC ACTIVE to AUTOMATIC INACTIVE.
NOTE: A module with a releasing Type ID can not be forced.
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A TUE JAN 25, 2011
CONTROL ON/OFF: N114L03M052
AUTOMATIC ACTIVE
ELEVATOR RECALL EAST WING
FIFTH FLOOR Z000 CONTROL
FORCE OFF BACK
NOTE: A module with a releasing Type ID cannot be forced.