Appendix D: Intelligent Sensing Applications
D.1 Intelligent Sensing Overview
Intelligent Sensing is a set of software algorithms that provide the NFS2-3030 with industry-
leading smoke detection capability. The user can program Intelligent Sensing functions on a global
or on a per-detector basis.
Intelligent Sensing topics covered in this appendix:
D.2 Intelligent Sensing Features
Intelligent Sensing features include the following:
Drift Compensation and Smoothing
Maintenance Warnings - Three Levels
Self-optimizing Pre-Alarm
Detector Sensitivity
Cooperative Multi-Detector Sensing
D.2.1 Drift Compensation and Smoothing
Drift compensation uses algorithms (U.S. patent pending) that identify and compensate for long-
term changes in the analog readings from each smoke detector. (Typically, dirt and dust
accumulation inside the smoke chamber causes long-term changes in detector readings.) Drift
compensation does the following:
Allows a detector to retain its original ability to detect actual smoke, and resi
st false alarms,
even as dirt and dust accumulates.
Reduces maintenance requirements by allowing the control panel to automatically perform
the periodic sen
sitivity measurements required by NFPA Standard 72.
The software also provides smoothing filters to remove transient
noise signals, usually caused by
electrical interference. Different smoothing algorithms are used, depending on the sensitivity
selection of each detector. Refer to Appendix D.4, “Detector Sensitivity Settings”, on page 124 for
more information on detector sensitivity levels.
Topic Page
Intelligent Sensing features – Descri
ptions of Intelligent Sensing features, such as
Drift Compensation, Sensitivity Adjust, programmable on a per-detector basis.
120
Pre-Alarm – Alert and Action settings, p
rogramming (global settings). 123
Detector Sensitivity Settings – Pre-
Alarm and Alarm sensitivity settings for photo, ion,
laser, and multisensor detectors programmable on a per-detector basis.
124
Detector Maintenance Features – Instructions
for viewing and printing detector
maintenance information.
126

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell nfs2-3030 and is the answer not in the manual?

Honeywell nfs2-3030 Specifications

General IconGeneral
BrandHoneywell
Modelnfs2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals