NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012 67
Autoprogram Menu Program
2. Physically install/uninstall the SLC devices.
3. Press the
AUTOPROGRAM LOOPS soft key to run the Autoprogram. Existing information
will not be changed.
Autoprogram will find the devices/modules on the selected installed SLCs. It will compare the
information it
finds during autoprogramming against any point information that may already be in
the database, and it will look for any addressing errors, such as two detectors with the same
address. If it finds a discrepancy or error, a screen will be displayed with the discrepant or incorrect
information and the programmer will be given the option of changing it.
Figure 3.57 Autoprogram Menu Screen
Soft Keys
AUTOPROGRAM LOOPS: Press to scroll through the options: ALL, 1+2, 3+4, 5+6, 7+8,
9+10. Stop at the desired option to select it.
ACCEPT: Press to autoprogram the selection. A confirmation screen will display asking the
p
rogrammer to confirm the autoprogram choice made (press the YES soft key to confirm). A screen
with the message AUTOPROGRAM IN PROGRESS will display until autoprogramming is complete.
3.6.3 Confirmation Screens
SLC Statistics
When autoprogramming is complete, the panel will display a list of the number of modules and
detectors found on each SLC. Refer to Figure 3.58 for an example of the screen.
AUTOPROGRAM MENU
AUTOPROGRAM LOOPS: ALL
ACCEPT
BACK