26 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Program Panel Program
SILENCEABLE WATERFLOW:If the SILENCEABLE WATERFLOW option is set to NO,
incoming Waterflow events will not be allowed to be silenced. If set to
YES, incoming Waterflow
events can be silenced.
Default:
NO
Reminder Menu
Press the Reminder Menu soft key on the Panel Program Menu 1 screen to set the trouble reminder.
Figure 3.13 Reminder Menu Screen
Soft Keys
TROUBLE REMI
NDER: Press this soft key to toggle between the two possibilities:
YES: Choose this to initiate a daily 11:00AM reminder that there are uncleared troubles in the
system. The reminder will appear on the screen and will sound a piezo (if the piezo is enabled).
NO: Choose this if no reminder is desired. Default: YES
ACCEPT: Press this
soft key to save the information entered on this screen.
3.2.5 Panel Timers (Menu 1)
Press the Panel Timers soft key on the Panel Program Menu 1 screen to display the following
screen.
Figure 3.14 Panel Timers (Menu 1) Screen
REMINDER MENU
TROUBLE REMINDER: YES
ACCEPT
BACK
PANEL TIMERS
VERIFY TIME: 30 VERIFY=PREALARM: NO
MAXIMUM VERIFICATION COUNT: 00
AC FAIL DELAY:
2 HOURS MORE
SILENCE INHIBIT:00:00 ACCEPT
AUTO SILENCE: OFF BACK