8 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Section 1: General Information
1.1 About This Manual
The following graphics appear in the manual to indicate a caution, a warning, or a note.
1.2 UL 864 Compliance
1.2.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864 9th Edition.
A complete listing identifying which products have
or have not received UL 864 9th Edition
certification is located in the installation manual of this fire alarm system. These products may only
be used in retrofit applications. Operation of the NFS2-3030 with products not tested for UL 864
9th Edition has not been evaluated and may not comply with NFPA 72 and/or UL 864. These
applications will require the approval of the local Authority Having Jurisdiction (AHJ).
1.2.2 Programming Features Subject to AHJ Approval
This product incorporates field-programmable software. The features and/or options listed below
must be approved by the local AHJ.
!
WARNING:
INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO
THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL
INJURY.
!
CAUTION:
INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS,
RUNTIME ERRORS, OR EQUIPMENT DAMAGE.
NOTE: Information that highlights an important part of the preceding or subsequent text or
illustration.
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control
Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not
used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
IP downloads over a local area network
(LAN) or the internet (Wide Area Network -
WAN)
No Yes
No
Timed
No
Releasing: Abort Switch Yes NYC
AHJ
ULI
IRI
ULI
IRI
Detector Programming: Supervisory Type
Codes
Yes SUP L(DUCTI)
SUP T(DUCTI)
SUP T(DUCTP)
SUP L(DUCTP)
SUP L(ION)
SUP T(ION)
SUP L(PHOTO)
SUP T(PHOTO)
SUP L(LASER)
SUP T(LASER)
P/CO (P SUP)
SUP L(DUCTI)
SUP T(DUCTI)
SUP L(DUCTP)
SUP T(DUCTP)