28 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Program Panel Program
3.2.6 Panel Timers (Menu 2)
Press the MORE soft key on the Panel Timers Menu 1 screen to display the following screen.
Figure 3.15 Panel Timers (Menu 2) Screen
Soft Keys
PAS: Press to toggle between the choices of OFF or ON for PAS (Positive Alarm Sequence). Refer
to Appendix C, “Special Zone Outputs” for an explanation of this option. Default: OFF
PRESIGNAL DELAY: Press to enter a
value of 00:00 (OFF) or a value of 1:00 to 3:00 minutes
(in the format MM:SS, where MM= minutes, SS=seconds). This feature initially causes alarm
signals to sound only in specific areas, monitored by qualified personnel. This allows delay of the
alarm for up to 3 minutes after the start of alarm processing. Refer to Appendix C, “Special Zone
Outputs” for further explanation of this option. Default: 3:
00
D
EFAULT TIMERS: Press this
soft key to activate default settings for the following:
ACCEPT: Press this
soft key to save the information entered on this screen and return to the
previous screen.
3.2.7 LCD Programming
The LCD Programming screen allows the user to vary the contrast of the display and turn the
backlight on or off.
Program setting for: Default:
Verify Time 30 seconds
Max. Verify 20
AC Fail Delay 8 hours
Silence Inhibit 0 (disabled)
Auto Silence Off
Verify=Prealarm No
PAS OFF
Presignal Delay 3 minutes
Table 3.4 Default Timers
PANEL TIMERS
PAS: OFF
PRESIGNAL DELAY: MM:SS
DEFAULT TIMERS
ACCEPT
BACK