Table 12-18 Setting alarm conditions for dry contact outputs
Main Menu Second-Level
Menu
Third-Level
Menu
Default Value Setting
Parameters
Settings
Alarm
Parameters
DO Dry Contact
Para.
ALM1 Alarm
Action
Close, Open
Table 12-19 Setting alarm conditions for dry contact inputs
Main Menu Second-Level
Menu
Third-Level
Menu
Default Value Setting
Parameters
Settings
Alarm
Parameters
DI Dry Contact
Para.
DIN1 Alm. Cond. Close, Open
----End
12.2.12 Setting Communications Parameters
IP Networking
Step 1 Set the IP type, IP address, subnet mask, and gateway address on the LCD.
Table 12-20 Setting IP parameters
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
Setting
Parameters
Settings
Comm.
Parameters
Network
Parameters
IP Type IPv4 Set this parameter
as required.
IP Address 192.168.0.10 Set this parameter
according to the
address information
provided by the
network
administrator.
Subnet Mask 255.255.255.0 Set this parameter
according to the
address information
provided by the
network
administrator.
PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide 12 Power-on and Commissioning
Issue 02 (2021-09-28) Copyright © Huawei Technologies Co., Ltd. 134