MD320/MD320N User Manual Parameter Description
137
F8-22
Earth short circuit protection
detection upon power-on
Factory default
value
1
Setup range
0:Inactive
1: Active
It can select whether the inverter checks the motor for earth short circuit failure upon power-on.
If this function is active, the inverter has short-time output at the instance of power-on.
F8-23
Running time to action
selection
Factory default
value
0
Setup range
0: Continue running
1: Stop
Group F9 Fault and Protection
F9-00
Motor
overload protection
selection
Factory default value 1
Setup range
:
0: Inactive
1:Active
0: The inverter has no overload protection
for the motor, and thermal relay is installed
before the motor.
1: The inverter has overload protection
function for the motor. Refer to F9-01 for
the protection value.
F9-01
Motor overload
protection gain
Factory default value 1.00
Setup range
:
0.20 ~ 10.00
The motor overload protection is inverter
time-lag curve; 220%×(F9-01)× rated motor
current: one minute; 150%×(F9-01)× rated
motor current: 60 minutes.