MD320/MD320N User Manual Safety and Precautions
15
1.2.10 Lightning Impulse Protection
The series inverter has lightning over current protection device, and has certain self-protection
capacity against the lightning. In applications where lightning occurs fre quently, the user shall
install additional protection devices at the front-end of the inverter.
1.2.11 Altitude and Derating
1.2.12 Certain Special Use
1.2.13 Note of Inverter Disposal
1.2.14 Adaptable Motor
In areas with altitude of more than 1,000 meters, the heat sinking effect of the inverter may
turn poorer due to rare air. Therefore, it needs to derate the inverter for use. Please contact our
company for technical consulting in case of such condition.
If the user needs to use the inverter with the methods other than the recommended wiring
diagram in this manual, such as shared DC bus, please consult our company.
The electrolytic capacitors on the main circuit and the PCB may explode when they are burnt.
Emission of toxic gas may be generated when the plastic parts are burnt. Please dispose the
inverter as industrial wastes.
1) The standard adaptable motor is four-pole squirrel-cage asynchronous induction motor. If
such motor is not available, be sure to select adaptable motors in according to the rated current
of the motor. In applications where drive permanent magnetic synchronous motor is required,
please consult our company;
2) The cooling fan and the rotor shaft of the non-variable-frequency motor adopt coaxial
connection. When the rotating speed is reduced, the cooling effect will be poorer. Therefore, a
powerful exhaust fan shall be installed, or the motor shall be replaced with variable-frequency
motor to avoid the over heat of the motor.
3) Since the inverter has built-in standard parameters of the adaptable motors, it is necessary
to perform motor parameter identification or modify the default values so as to comply with
the actual values as much as possible, or it may affect the running effect and protection
performance;
4)The short circuit of the cable or motor may cause alarm or explosion of the inverter.
Therefore, please conduct insulation and short circuit test on the newly installed motor and
cable. Such test shall also be conducted during routine maintenance. Please note that the
inverter and the test part shall be completely disconnected during the test.