FC-15
MS speed 15 Factory default value 0.0Hz
Setup range Negative maximum frequency to maximum frequency
When the frequency source parameters F0-07, F0-03 and F0-04 are determined as PLC
running mode, it needs to set FC-00 to FC-15, FC-16, FC-17 and FC-18 to FC-49 to determine
its characteristics.
Caution: The symbols of FC-00 to FC-15 determine the running direction of simple PLC. If they
are negative values, it indicates reverse direction.
The simple PLC is as shown in the following gure:
Fig.6-18 Schematic Diagram of Simple PLC
FC-16
PLC running mode Factory default value 0
Setup range
0 Stop upon completion of one-time running
1
Keep final value upon completion of one-time
running
2 Constant circulation
FC-17
PLC power-failure memory
selection
Factory default value 0
Setup range
0 Power failure without memory
1 Power failure with memory
0: Stop upon completion of one-time running
The inverter will automatically stop upon completion of one single cycle, and will not restart until
another running command is given.
1: Keep nal value upon completion of one-time running
The inverter will automatically keep the running frequency and direction of last one segment
upon completion of one single cycle.
2: Constant circulation