Function library
Free connection of digital signals, message output
7−79
L
EDB82MV752 EN 5.2
Selection under C0415/x Relays/digital output (not inverted)
32 Digital input X3/E1
Picks up/HIGH, if HIGH level is applied to the
corresponding digital input
33 Digital input X3/E2
34 Digital input X3/E3
35 Digital input X3/E4
36 (A) Digital input X3/E5
37 (A) Digital input X3/E6
38 PTC input X2.2/T1, X2.2/T2 Picks up/HIGH, if the potential−free switch is connected
to X2.2/T1, X2.2/T2
40 ... 55 AIF control word (AIF−CTRL) Bit 0 ... Bit 15
Picks up/HIGH, if the corresponding bit is set
60 ... 75 CAN−IN1.W1 or FIF−IN.W1 bit 0 ... bit 15
80 ... 95 CAN−IN1.W2 or FIF−IN.W2 bit 0 ... bit 15
100 ... 115 CAN−IN2.W1 bit 0 ... bit 15
120 ... 135 CAN−IN2.W2 bit 0 ... bit 15
140 Torque threshold 1 reached (MSET1=MOUT)
Picks up/HIGH, if the condition is met
141 Torque threshold 2 reached (MSET2=MOUT)
142 Process controller output limit reached (PCTRL1−LIM)
7.11.3 Free configuration of digital process data output words
Description
The digital process data output words can be freely assigned to internal digital signals. With
this you can summarise status information which will be automatically assigned to status word
bits:
– The configuration under C0417 is mapped to the AIF status word 1 (C0150), FIF output word
1 (FIF−OUT.W1) and output word 1 of the CAN object 1 (CAN−OUT1.W1).
– The configuration under C0418 is mapped to the AIF status word 2 (C0151), FIF output word
2 (FIF−OUT.W2) and output word 1 of the CAN object 2 (CAN−OUT2.W1).
A signal source can be assigned to several targets.