Commissioning
Vector control
5−10
L
EDB82MV752 EN 5.2
5.5 Commissioning − vector control
5.5.1 Commissioning without function module
Stop !
The controller can only be used when the FIF cover is mounted!
If the FIF cover is missing, the green LED is blinking (keypad: ). The controller is
inhibited.
The FIF cover is mounted when the inverter is delivered.
Since the controller is not provided with control terminals when the function module is not
attached, starting and stopping during operation is also possible by switching the mains.
Frequent mains switching (e.g. inching mode via mains contactor) may overload and destroy
the input current limitation of the controller: for this reason, at least three minutes have to
pass between two starting operations.
The function saves the setpoint at the time the operation is interrupted when switching the
mains or in case of mains failures. The drive restarts automatically as soon as the mains
recovers.
If the drive does not start after the setpoint has been selected, ( does not go off), press
to enable the controller.
1. Connect the keypad
2. Ensure that controller inhibit is active after mains connection
misc001
20 28
X3
}
Terminal X3/28 = LOW
3. Switch on the mains
ON
misc002
4. The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)
000
000
abcd e
mno
p
qr
Hi
Hz
Lo
1
j
gfkih PS
0050
The USEr menu is active
5. Go to the ALL menu
6. Change to the mode to configure the basic settings for
your drive
000
000
a
bcd e
mno
p
qr
Hi
Hz
Lo
1
j gfkih PS
0050
z
y
wx
Blinking on the display: 0050
7. Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
8. Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
9. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f
[ H z ]
f
2
C 0 0 1 1
f
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
t
ir
C0011
f
2
f
1
t
ir
= acceleration time wanted
10. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
t
if
C0011
f
2
f
1
t
if
= deceleration time wanted