Commissioning
Vector control
5−12
L
EDB82MV752 EN 5.2
5.5.2 Commissioning with standard I/O function module
The following instructions apply to controllers equipped with a standard−I/O function module and a
three−phase AC motor which has been selected according to a power−based assignment.
1. Connect the keypad
2. Ensure that controller inhibit is active after mains connection
misc001
20 28
X3
}
Terminal X3/28 = LOW
3. Switch on the mains
ON
misc002
4. The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)
000
000
abcd e
mno
p
qr
Hi
Hz
Lo
1
j
gfkih PS
0050
The USEr menu is active
5. Go to the ALL menu
6. Change to the mode to configure the basic settings for
your drive
000
000
a
bcd e
mno
p
qr
Hi
Hz
Lo
1
j gfkih PS
0050
z
y
wx
Blinking on the display: 0050
7. Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpoint selection
E2: JOG2/3
E3: DCB DC injection brake
E4: CW/CCW rotation
z
y
wx
0
000
a
bcd e
mno
p
qr
Hi
Lo
1
j gfkih PS
0007
8. Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
9. Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
f
[ H z ]
f
2
C 0 0 1 1
f
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
t
ir
C0011
f
2
f
1
t
ir
= acceleration time wanted
11. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
t
if
C0011
f
2
f
1
t
if
= deceleration time wanted
12. Activate the control mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
E82ZBC014
z
y
wx
v
t
u
s
4
00
1
4
000
1
cd
f
PS
p
Para
H/L
SubcodeDispSet
13. Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
z
y
wx
0
000
abcd e
mno
p
qr
Hi
Lo
1
j gfkih PS
0034
Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for the
standard I/O)
14. Enter the motor data See motor nameplate
A Rated motor speed (C0087)
Lenze setting: 1390 rpm
B Rated motor current (C0088)
Lenze setting: Depends on the controller
Enter the value for the motor connection type
(star/delta) selected!
C Rated motor frequency (C0089)
Lenze setting: 50 Hz
D Rated motor voltage (C0090)
Lenze setting: Depends on the controller
Enter the value for the motor connection type
(star/delta) selected!
E Motor−cos (C0091)
Lenze setting: Depends on the controller