[ I Read Before Servicing ]
- 5 -
HWE10060 GB
[3] Brazing
No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide
scale, water, and dust) out of the refrigerant system.
Example: Inside the brazed connection
1. Items to be strictly observed
Do not conduct refrigerant piping work outdoors if raining.
Use non-oxidized solder.
Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and
copper coupling.
If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
2. Reasons
The new refrigerating machine oil is 10 times as hygroscopic as the conventional oil and is more likely to cause unit failure if
water infiltrates into the system.
Flux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.
3. Notes
Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to
deteriorate.
Use of oxidized solder for brazing Use of non-oxidized solder for brazing

Table of Contents

Other manuals for Mitsubishi Electric CAHV-P500YA-HPB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric CAHV-P500YA-HPB and is the answer not in the manual?

Mitsubishi Electric CAHV-P500YA-HPB Specifications

General IconGeneral
BrandMitsubishi Electric
ModelCAHV-P500YA-HPB
CategoryHeat Pump
LanguageEnglish

Related product manuals