EasyManuals Logo

Mitsubishi Electric CAHV-P500YA-HPB Service Handbook

Mitsubishi Electric CAHV-P500YA-HPB
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
[ IV Remote Controller ]
- 47 -
HWE10060 GB
Settings details
[4]-1. Display language setting
The display language can be selected from the languages listed below.
Press the [ MENU] button to change the language.
English (GB), German (D), Spanish (E), Russian (RU),
Italian (I), French (F), Swedish (SW)
[4]-2. Function lock settings
(1) Function lock
Press the [ ON/OFF] button to toggle through the following options.
* Press and hold the [CIR.WATER] and [ ON/OFF] buttons
simultaneously for two seconds on the Normal Operation screen to enable
the button-lock function.
(2) Operation mode skip setting
The following modes can be made available for selection or can be hidden.
Press the [ ON/OFF] button to toggle through the following options.
* The mode that is not supported on the connected unit will not be available,
even if the mode is available for selection on the display.
(3) Temperature range limit setting
The temperature range for the following modes can be restricted. Once the
range has been restricted, the preset temperature can only be set to a value
within the restricted range.
Press the [ ON/OFF] button to toggle through the following options.
To increase or decrease the temperature, press the [ TEMP. or
] button.
Settable range
* The settable range varies depending on the type of unit to be connected.
[4]-3. Basic functions
(1) Remote controller main/sub setting
Press the [ ON/OFF] button to toggle between the following options.
(2) Use of clock setting
Press the [ ON/OFF] button to toggle between the following options.
(3) Timer function setting
Press the [ ON/OFF] button to toggle through the following options.
* When the use of clock setting is set to OFF, the “WEEKLY TIMER” cannot
be used.
(4) Contact number setting
Press the [ ON/OFF] button to toggle through the following options.
Setting the contact number
To set the contact number, follow the following procedures.
Press the [ TEMP. or ] button to move the cursor to the
right (left). Press the [ CLOCK or ] button to set the
contact number.
(5) Temp offset setting
Press the [ ON/OFF] button to toggle between the following options.
[4]-4. Display options
(1) Temperature unit °C/°F setting
Press the [ ON/OFF] button to toggle between the following options.
(2) Water temperature display setting
Press the [ ON/OFF] button to toggle between the following options.
no1: All buttons except the [ ON/OFF] button will be locked.
no2: All buttons will be locked.
OFF (Default): No buttons will be locked.
Heating mode
Heating ECO mode
Hot Water mode
Anti-freeze mode
Cooling mode
OFF (Default): All modes will be available for selection.
LIMIT TEMP HEATING MODE
LIMIT TEMP HOT WATER MODE
LIMIT TEMP ANTI-FREEZE MODE
LIMIT TEMP COOLING MODE
OFF (Default) : The temperature ranges are not active.
Hot Water mode : Lower limit:
Upper limit:
25 ~70 °C
70 ~25 °C
(77 ~158 °F)
(158 ~ 77 °F)
Heating mode : Lower limit:
Upper limit:
25 ~55 °C
55 ~25 °C
(77 ~131 °F)
(131 ~ 77 °F)
Main The controller will be designated as the main controller.
Sub The controller will be designated as the sub controller.
ON The clock function.
OFF The clock function.
WEEKLY TIMER (Default)
AUTO OFF TIMER
SIMPLE TIMER
TIMER MODE OFF
CALL OFF The contact number will not be displayed when a
problem occurs.
CALL **** *** **** The contact number will be displayed when a
problem occurs.
CALL_ Use this option to enter the contact number.
ON The offset value will be displayed under the water
temperature initial setting mode.
OFF The offset value will not be displayed.
°C Celcius
°F Fahrenheit
ON The water temperature will be displayed.
OFF The water temperature will not be displayed.
1234
56 7
1
2
3
1
2
3
4
5
1
2
3
4
5
6
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
4
D
D
D
D
D
D
D
F
C

Table of Contents

Other manuals for Mitsubishi Electric CAHV-P500YA-HPB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric CAHV-P500YA-HPB and is the answer not in the manual?

Mitsubishi Electric CAHV-P500YA-HPB Specifications

General IconGeneral
BrandMitsubishi Electric
ModelCAHV-P500YA-HPB
CategoryHeat Pump
LanguageEnglish

Related product manuals