[ VII Control ]
- 74 -
HWE10060 GB
(6) Selecting the item that normally appears on the LED
(*1)
(*2)
SW2 SW3
Display content
-10 5 6 7 8 9 10
OFF OFF OFF ON OFF OFF OFF Displays the operation mode.(*1)
OFF OFF ON ON OFF OFF OFF Displays the operation mode.(*2)
OFF ON ON OFF OFF OFF OFF Displays the current water temperature.
OFF ON OFF OFF OFF OFF OFF Displays the water-temperature setting.
OFF OFF OFF OFF OFF OFF OFF Displays the high and low refrigerant pressures.
The dot lights up when the operation signal is on.
The dot lights off when the operation signal is off.
"A" will be displayed while the compressor is in operation.
"S" will be displayed while the compressor is stopped.
"S" will be displayed while the fan is forced to operate.
"-" will be displayed when this function is disabled.
"d" will be displayed when the peak-demand control function is enabled.
"-" will be displayed when this function is disabled.
Displays the operation mode.
"H" will be displayed during water-heating operation.
"d" will be displayed during a defrost cycle.
"F" will be displayed while the pump is being operated to prevent freeze-up.
Displays the system control mode.
"S" will be displayed when the multiple system control option is used.
"A" will be displayed when the individual system control option is used.

Table of Contents

Other manuals for Mitsubishi Electric CAHV-P500YA-HPB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric CAHV-P500YA-HPB and is the answer not in the manual?

Mitsubishi Electric CAHV-P500YA-HPB Specifications

General IconGeneral
BrandMitsubishi Electric
ModelCAHV-P500YA-HPB
CategoryHeat Pump
LanguageEnglish

Related product manuals