[ VII Control ]
- 84 -
HWE10060 GB
-9- Anti-short-cycling protection
The unit has a function to keep the compressor from short-cycling when the amount of circulating water is low or when the
load is light. After the compressor cycles off, it will not restart for 10 minutes.
The unit has a 3-minute restart-delay function to protect
the compressor from short-cycling. This function is effec-
tive even after a power failure.
Compressor
ON
OFF
Time
Min. 3 minutes
3-minute restart delay function
The 3-minite restart-delay function will
be triggered in the following situations:
(1) The setting for the SWS1 (Local,
Off, Remote) was changed, or (2) after
a power failure.
Min. 10 minutes 15 minutes 10 minutes
Compressor
ON
ON for
7 minutes
ON for
12 minutes
ON for
6 minutes
ON for
4 minutes
3 minutes3 minutes
OFF
Time