PARAMETERS
154
Pr. 7 "acceleration time"
Pr. 8 "deceleration time"
Pr. 44 "second acceleration/
deceleration time"
Pr. 45 "second deceleration
time"
Related parameters
4.2.48 Stop selection (Pr. 250)
Pr. 250 "stop selection"
Used to select the stopping method (deceleration to a stop or coasting) when the start
signal (STF/STR) switches off.
Parameter
Number
Factory
Setting
Setting Range
250 9999
0 to 100 s, 1000 to
1100 s, 8888, 9999
(1)Pr. 250 = "9999"
When the start signal switches off, the motor is decelerated to a stop.
Time
Output
frequency
(Hz)
ON
OFF
Start si
g
nal
Decelerated when start signal switches off.
Deceleration time (time set in Pr. 8, etc.)
DC brake
(2)Pr. 250 = 0 to 100 seconds (output is shut off after preset time)
The output is shut off when the time set in Pr. 250 has elapsed after the start signal
was switched off. The motor coasts to a stop.
OFF
Start si
g
nal
Output is shut off when time set in Pr. 250
has elapsed after start si
g
nal was switched
off.
Output
frequency
(Hz)
Motor coasts to a stop.
Time
OFF
RUN signal