125
Built-in Inputs Section 6-1
Procedure
Restrictions on General-purpose Inputs
General-purpose inputs 0 to 3 cannot be used when built-in inputs IN0 to
IN3 are being used as interrupt inputs or quick-response inputs.
General-purpose inputs 8 and 9 cannot be used when high-speed
counter input 0 is being used. Furthermore, general-purpose input 3 can-
not be used if the high-speed counter 0 reset method is set to Phase-Z
signal + Software reset.
General-purpose inputs 6 and 7 cannot be used when high-speed
counter input 1 is being used. General-purpose input 2 cannot be used if
the high-speed counter 1 reset method is set to Phase-Z signal + Soft-
ware reset.
General-purpose inputs 0 and 1 cannot be used when the origin search
function is enabled for pulse output 0 (enabled in the PLC Setup). Also,
general-purpose input 4 cannot be used when operating mode 2 has
been specified, i.e., the Positioning Completed Signal is being used.
General-purpose inputs 2 and 3 cannot be used when the origin search
function is enabled for pulse output 1 (enabled in the PLC Setup). Also,
general-purpose input 5 cannot be used when operating mode 2 has
been specified, i.e., the Positioning Completed Signal is being used.
Select general purpose
Wire inputs.
PLC Setup settings
Ladder program
IN0 to IN9 (CIO 2960 bits 00 to 09)
Connect to the selected terminals between IN0 and IN9.
When IN0 to IN3 are used as general-purpose inputs, make
the necessary "input operation settings" for IN0 to IN3 in
Programming Console address 60.
IN0: Set the rightmost digit (bits 00 to 03) to 0.
IN1: Set the second digit (bits 04 to 07) to 0.
IN2: Set the third digit (bits 08 to 11) to 0.
IN3: Set the leftmost digit (bits 12 to 15) to 0.
The default setting for address 60 is 0000 (inputs IN0 to IN3
used as general-purpose inputs.)
When setting the input time constant (ON response time),
make the necessary "input time constant setting" in
Programming Console address 61. The input time constant
setting applies to general-purpose inputs IN 0 to IN9 only.
00 hex: Default (8 ms); 10 hex: No filter; 11 hex: 0.5 ms; 12
hex: 1 ms; 13 hex: 2 ms; 14 hex: 4 ms; 15 hex: 8 ms; 16 hex:
16 ms; 17 hex: 32 ms
Use the general-purpose inputs in instructions such
as LD.
To use the immediate-refreshing variation, add the
"!" prefix to the instruction. For example: !LD.
Note: Immediate refreshing cannot be performed by the
IORF(097) instruction.