Restart Functions
This section describes the restart-related functions and their operations.
7-4-1
Restart Settings
• Whether or not to perform an auto search start during restart is determined based on the setting of
Motor Starting Mode Auto Search Function Selection (H09). If auto search start is not to be per-
formed, the inverter restarts from the starting frequency as in normal operation.
• If “0: Disable” is set at Motor Starting Mode Auto Search Function Selection (H09), then Power Inter-
ruption Restart Wait Time (H13) is ignored, and restart is performed from 0 Hz.
• If “2: Enable at normal start and restart after momentary power failure” is selected for Motor Starting
Mode Auto Search Function Selection (H09), auto search restart is performed even when the power
is turned ON again.
• H09 is a parameter that is used in V/f control (including dynamic torque vector control). Motor Start-
ing Mode Auto Search in Speed Sensor less Vector Control (d67) is used during vector control with-
out sped sensor.
• When vector control with speed sensor is used, restart is performed from the speed detected by the
speed sensor regardless of Motor Starting Mode Auto Search Function Selection (H09).
• When using V/f control with speed sensor (including dynamic torque vector control with speed sen-
sor), Motor Starting Mode Auto Search Function Selection (H09) is followed.
Parameter No. Function name Data Default data Unit
H09
Motor Starting Mode
Auto Search Function
Selection
0: Disable
1: Enable only at restart after momen-
tary power failure
2: Enable at normal start and restart
after momentary power failure
0 -
d67
Motor Starting Mode
Auto Search in Speed
Sensor less V
ector
Control
1 -
• The details of Starting Frequency Selection at Frequency Pull-in Restart (E152) are as follows.
Set value Description Description
0
Frequency at which the pow-
er failure occurred
Pull-in from frequency when inverters output was
shut off
1 Maximum frequency Pull-in from maximum frequency
2 Set frequency Pull-in from currently selected frequency reference
3 Starting frequency Restart from starting frequency
7-4-2
Restart after Momentary Power Failure
This function is used to set operation selection during restart after a momentary power failure.