Planning the MOBY D system
4.5 EMC Guidelines
MOBY D
76 System Manual, 01/2010, J31069-D0147-A6-7618
Prevention of interference by optimum configuration
Good interference suppression can be achieved by installing SIMATIC PLCs on conducting
mounting plates (unpainted). When setting up the control cabinet, interference can be
prevented easily by observing certain guidelines. Power components (transformers, drive
units, load power supply units) should be arranged separately from the control components
(relay control unit, SIMATIC S7).
As a rule:
The effect of the interference decreases as the distance between the interference source
and interference sink increases.
The interference can be further decreased by installing grounded shielding plates.
The load connections and power cables should be installed separately from the signal
cables with a minimum clearance of 10 cm.
3RZHUVXSSO\
&&(8
'ULYH
6KLHOG
SODWH
Figure 4-25 Prevention of interference by optimum configuration

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC MOBY D and is the answer not in the manual?

Siemens SIMATIC MOBY D Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC MOBY D
CategoryAccessories
LanguageEnglish

Related product manuals