09.2008 Communication / PROFIBUS
Siemens AG 6SE7087-6QX70 (Version AK)
SIMOVERT MASTERDRIVES Compendium Motion Control 8.2-137
8.2.10.7 Extended CBP2 diagnosis for start-up personnel
Activation of the extended diagnosis with P711.x > 0
Image of the C1 master telegrams
P711.x Display in r732.9..24 (32 bytes)
1 Output: PKW and setpoints from the master Maximum 32 bytes
2 Input: PKW and actual values to the master Maximum 32 bytes
3 Byte 0 – 31
50 Byte 32 - 63
51 Byte 64 - 95
52 Byte 96 - 127
53 Byte 128 - 159
54 Byte 160 - 191
55 Byte 192 - 223
56
Configuring telegram from the master
End identifier: 0x5A, 0xA5
Byte 224 - 244
4 Byte 0 – 31
60 Byte 32 - 63
61 Byte 64 - 95
62 Byte 96 – 127
63 Byte 128 – 159
64 Byte 160 – 191
65 Byte 192 – 223
66
Parameterizing telegram from the master
End identifier: 0x5A, 0xA5
Byte 224 – 244
Diagnosis of configuration and parameterization
P711.x r732.x
30 r732.9 Result of parameterizing telegram evaluation (see table)
r732.10 Result of evaluating cross-traffic parameterization (see table)
r732.11 Result of configuring telegram evaluation (see table)
r732.12 PPO type 1-5; if free configuration, then 0xff
r732.13 Length of the input data to the master (without PKW) in bytes
r732.14 Length of the output data from the master (without PKW) in bytes
r732.15 Double-word specifier setpoints
r732.16 Double-word specifier actual values
r732.17 Free memory in the multi-port RAM of the DPC31 in bytes
The value output in parameter P732.9 (P711.x = 30) arises due to bit-by-
bit OR linking of the following parameters. In the case of errors in the
block for cross-traffic parameterization, the detailed fault codes are to be
entered in parameter P732.10. Only if P732.10 contains the value 0 can
the clear causes of the fault be read out of P732.9. If P732.10 <> 0, the
content of P732.9 is falsified and the errors leading to abort cannot be
clearly determined!

Table of Contents

Other manuals for Siemens simovert masterdrives

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simovert masterdrives and is the answer not in the manual?

Siemens simovert masterdrives Specifications

General IconGeneral
BrandSiemens
Modelsimovert masterdrives
CategoryDC Drives
LanguageEnglish

Related product manuals