Field Start-up
Information Manual 31
ICS Address
Range of values is 1 to 127 in increments of 1.
Factory Default is 65.
Power Up Start Delay Time
Range of values is 0 to 600 seconds in increments of
1. Factory Default is 0 sec.
Design Delta Temperature Setpoint
Range of values is 4 to 30°F (2.2 to 16.7°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
10°F (5.5°C).
Leaving Water Temperature Cutout
Setpoint
Range of values is -10 to 36°F (-23.3 to 2.2°C) in
increments of 1 or 0.1 °F or °C depending on the
Service Setup Screen xxx or xxx.x. The Factory
Default is 36.0°F (2.2°C).
When this setpoint is within 1.7°F of the Front Panel
Chilled Water Setpoint, the Front Panel Chilled
Water Setpoint is increased along with this setpoint
to maintain the differential. A message will be
displayed for 2 seconds to indicate that the FPCW
setpoint has been increased.
When this setpoint is adjusted below 35.3°F the
following is displayed on the second line:
Low Refrigerant Temperature Cutout
Setpoint
Range of values is -35 to 36°F (-37.2 to 2.2°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. The Factory
Default is 32.0°F (0.0°C).
Low Evaporator Water Flow Warning Setpoint
The following will be displayed only if the Differential
Water Sensing Option is installed.
Range of values is 0.0 to 4.0 gpm/ton (0.0 to 15.1
lpm/ton) in increments of 0.1. Factory Default is 1.2
gpm/ton (4.5 lpm/ton).
Condenser Limit Setpoint
Range of values is 80 to 120% in increments of 1%.
Factory Default is 93%.
Maximum Restart Inhibit (RI) Timer
Setting
The Range of values is 30 to 60 Minutes in
increments of 1 Minute. Factory Default is 60
Minutes.
ICS Address: xx
Press (+)(-) to Change Setting
Power Up Start Delay Time: xxx sec
Press (+)(-) to Change Setting
Design Delta Temp Setpoint: xxx.x f/c
Press (+)(-) to Change Setting
Lvg Wtr Temp Cutout Setpoint:xxx.x f/c
Press (+)(-) to Change Setting
“Warning: Adequate Antifreeze Required”.
Low Rfgt Temp Cutout Setpt: xxx.x f/c
Press (+)(-) to Change Setting
Low Evap Flow Warning: xx.x gpm/ton
Press (+)(-) to Change Setting
Condenser Limit Setpoint: xx % HPC
Press (+)(-) to Change Setting
Maximum RI Timer: xxx Minutes
Press (+)(-) to Change Setting