Refrigerant Monitor Calibration
54 CVHE-CLD-1A
If the refrigerant monitor is unable to calibrate, the
following item is displayed.
Otherwise, the following screens continue.
This item is followed by one of the following two
items.
If the <Enter> key is pressed, the display will return
to the second menu item above. If the <Cancel> key
is pressed, the display continues to the next display.
Refrigerant Span Calibration
If <Next> is pressed the following refrigerant span
calibration screens are skipped. If <Enter> is pressed
the following screens are displayed to permit
refrigerant span calibration.
If the refrigerant monitor is unable to calibrate, the
following item is displayed.
Otherwise, the following screens continue.
If the refrigerant monitor is unable to calibrate, the
following item is displayed.
Otherwise, the following screens continue.
Unable to Calibrate
Refrigerant Zero Calibration XXXX
Press (Enter)(Cancel)(+)(-) To Continue
Starting The Calibration Procedure
Please Wait
Successful Calibration
Calibration Failed
(Enter) To Retry, (Cancel) To Exit
Refrigerant Span Calibration
(Enter) to Start, (Next) to Continue
Starting The Calibration Procedure
Please Wait
Unable to Calibrate
Connect Refrigerant Span Gas
(Next) To Continue, (Cancel) To Exit
Open Gas Sample Valve
(Next) To Continue, (Cancel) To Exit
XXXX PPM [Rfgt Type]
(Enter) To Adjust Conc, (Cancel) to Exit
Locking The Reading
Please Wait
Unable to Calibrate
Refrigerant Span Calibration XXXX
Press (Enter)(Cancel)(+)(-) To Continue
Starting The Calibration Procedure
Please Wait