Information Manual 83
FastPak™ “Settings Group” Menu Record
Field Startup Group:
Menu item Choices Default Design/Actual
1 Keypad/Display Lock Feature Enable Disable, Enable Disable
2 Menu Settings Password Enable Disable, Enable Disable
3 ICS Address: 1 to 127 65
4 Power Up Start Delay Time 0 to 60° Seconds 0 Seconds
5 Design Delta Temp Setpoint: 4 to 30°F, 2.2 to 16.7° C 100° F, 5.5 °C
6 Lvg Wtr Temp Cutout Setpoint: (When this
setpoint is within 1.7°F of the Front Panel
Chilled Water Setpoint, the Front Panel
Chilled Water Setpoint is increased along
with this setpoint to maintain the differential)
-10 to 360°F,
-23.2 to 2.2° C
36° F, 2.2° C
7 Low Rfgt Temp Cutout Setpt: (When this
setpoint is within 6°F of the Front Panel
Chilled Water Setpoint, the Front Panel
Chilled Water Setpoint is increased along
with this setpoint to maintain the differential.)
-35 to 360°F,
-37.2 to 2.2°C
32°F, 0.0°C
8 Condenser Limit Setpoint: 80 to 120% 93%
9 Maximum RI Timer Setting 30 to 60 Minutes 60 Minutes
10 Purge Control/Type: Micro Purge, Stand-Alone
Purge
Micro Purge
11 Purge Max Pumpout Rate: 1 to 100 minutes/24 hrs 20 Minutes /24
Hours
12 Purge Service Excessive Pumpout Override
Timer
1 to 72 Hours 0 Hours
13 Prg Low Liq Temp Inhibit Enable, Disable Disable
14 Prg Low Liq Temp Inhibit Setpt: (Does not
display unless above feature = Enable”)
32 to 50 °F, 0.0 to 10 °C 40°F, 4.4°C
15 Surge Protection: Disable, Enable Enable
16 Under/Over Voltage Protection: (Permits
“Enable only if Option Installed)
Disable, Enable Enable
17 Phase Reversal Protection: Disable, Enable Enable
18 Phase Unbalance Protection: Disable, Enable Enable
19 Momentary Power Loss Protection: Disable, Enable Enable
20 Enhanced Oil Temp Protection Disable, Enable Enable
21 Oil Temp Setpoint: 100 to 160° F, 37.8 to
71.1°C
143.5°F,61.9°C
22 Low Oil Temp Cutout: 80 to 140 °F, 26.7 to 60°C 95 °F, 35°C
23 High Discharge Temp Cutout: 170 to 220°F, 76.6 to
104.4 °C
200°F, 93.3 °C
24 Soft Load Control: Disable, Enable Disable
25 Soft Load Starting current Limit: 40 to 100% 100%
26 Soft Load Current Limit Rate: 0.5 to 5.0% /Minute 5.0% /Minute
27 Soft Load Lvg Water Rate: 0.5 to 5.0 °F/Minute
0.3 to 2.8
0
C/Minute
5.0°F/Minute
2.8°C/Minute