CL settings
224
1SVC 440 795 M0100
Changing the operating mode or the circuit diagram
When the operating mode is changed or the CL circuit
diagram is modified, the retentive data is normally saved
together with their actual values. The actual values of relays
no longer being used are also retained.
Changing the operating mode
If you change from RUN to STOP and then back to RUN, the
actual values of the retentive data will be retained.
Changing the CL circuit diagram
The actual values are retained if the CL circuit diagram is
modified.
Changing the startup behaviour in the SYSTEM menu
The retentive actual values in the logic relay are retained,
irrespective of the RUN MODE or STOP MODE setting.
h
Attention!
Even if the markers and function relays that were selected
as retentive are deleted from the circuit diagram, the
retentive actual values are retained when switching from
STOP to RUN or when switching the power supply off and
on again. If these relays are used in the circuit diagram
again, they will be assigned with the previous actual
values.