Name Type Description
TEMP REAL Calculated temperature of the device
TEMPAMB REAL Ambient temperature used in the calculations
TERMLOAD REAL Temperature relative to operate temperature
6.6.5 Settings
Table 59: LFPTTR (26) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
TRef 0 - 600 Deg F 1 160 End temperature rise above ambient of the line
when loaded with IRef
IRef 0 - 400 %IB 1 100 Load current in % of IBase leading to TRef
temperature
Tau 1 - 1000 Min 1 45 Time constant of the line
AlarmTemp 0 - 400 Deg F 1 175 Temperature level for pickup (alarm)
TripTemp 0 - 600 Deg F 1 195 Temperature level for trip
ReclTemp 0 - 600 Deg F 1 170 Temperature for reset of lockout after trip
AmbiSens Disabled
Enabled
- - Disabled External temperature sensor available
DefaultAmbTemp -50 - 250 Deg F 1 60 Ambient temperature used when AmbiSens is
set to Off
DefaultTemp -50 - 600 Deg F 1 100 Temperature raise above ambient temperature
at startup
Table 60: LFPTTR (26) Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
Table 61: LCPTTR (26) Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
TRef 0 - 300 Deg C 1 90 End temperature rise above ambient of the line
when loaded with IRef
IRef 0 - 400 %IB 1 100 Load current in % of IBase leading to TRef
temperature
Tau 1 - 1000 Min 1 45 Time constant of the line