10.3.5.2 Functionality
The Bay control QCBAY function is used together with Local remote and local remote
control functions to handle the selection of the operator place per bay. QCBAY also
provides blocking functions that can be distributed to different apparatuses within the bay.
10.3.5.3 Function block
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
IEC09000080_1_en.vsd
IEC09000080 V1 EN
Figure 112: QCBAY function block
10.3.5.4 Signals
Table 185: QCBAY Input signals
Name Type Default Description
LR_OFF BOOLEAN 0 External Local/Remote switch is in Off position
LR_LOC BOOLEAN 0 External Local/Remote switch is in Local position
LR_REM BOOLEAN 0 External Local/Remote switch is in Remote position
LR_VALID BOOLEAN 0 Data representing the L/R switch position is valid
BL_UPD BOOLEAN 0 Steady signal to block the position updates
BL_CMD BOOLEAN 0 Steady signal to block the command
Table 186: QCBAY Output signals
Name
Type Description
PSTO INTEGER Value for the operator place allocation
UPD_BLKD BOOLEAN Update of position is blocked
CMD_BLKD BOOLEAN Function is blocked for commands
LOC BOOLEAN Local operation allowed
REM BOOLEAN Remote operation allowed
Section 10 1MRK 511 287-UUS A
Control
256
Technical manual