Name Values (Range) Unit Step Default Description
AlarmTemp 0 - 200 Deg C 1 80 Temperature level for pickup (alarm)
TripTemp 0 - 300 Deg C 1 90 Temperature level for trip
ReclTemp 0 - 300 Deg C 1 75 Temperature for reset of lockout after trip
AmbiSens Disabled
Enabled
- - Disabled External temperature sensor available
DefaultAmbTemp -50 - 100 Deg C 1 20 Ambient temperature used when AmbiSens is
set to Off
DefaultTemp -50 - 300 Deg C 1 50 Temperature raise above ambient temperature
at startup
Table 62: LCPTTR (26) Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
6.6.6 Monitored data
Table 63: LFPTTR (26) Monitored data
Name
Type Values (Range) Unit Description
TTRIP INTEGER - - Estimated time to trip (in min)
TENRECL INTEGER - - Estimated time to reset of
lockout (in min)
TEMP REAL - Temperature
Fahrenheit
Calculated temperature of the
device
TEMPAMB REAL - Temperature
Fahrenheit
Ambient temperature used in
the calculations
Table 64: LCPTTR (26) Monitored data
Name
Type Values (Range) Unit Description
TTRIP INTEGER - - Estimated time to trip (in min)
TENRECL INTEGER - - Estimated time to reset of
lockout (in min)
TEMP REAL - deg Calculated temperature of the
device
TEMPAMB REAL - deg Ambient temperature used in
the calculations
Section 6 1MRK 511 287-UUS A
Current protection
132
Technical manual