6.11.2.2 Function block
ANSI08000506-1-en.vsd
GOPPDOP (32)
I3P*
V3P*
BLOCK
BLK1
BLK2
TRIP
TRIP1
TRIP2
BFI_3P
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI08000506 V1 EN
Figure 64: GOPPDOP (32) function block
6.11.2.3 Signals
Table 91: GOPPDOP (32) Input signals
Name Type Default Description
I3P GROUP
SIGNAL
- Three phase group signal for current inputs
V3P GROUP
SIGNAL
- Three phase group signal for voltage inputs
BLOCK BOOLEAN 0 Block of function
BLK1 BOOLEAN 0 Block of step 1
BLK2 BOOLEAN 0 Block of step 2
Table 92: GOPPDOP (32) Output signals
Name
Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip signal from stage 1
TRIP2 BOOLEAN Trip signal from stage 2
BFI_3P BOOLEAN General pickup signal
PICKUP1 BOOLEAN Pickup signal from stage 1
PICKUP2 BOOLEAN Pickup signal from stage 2
P REAL Active Power
PPERCENT REAL Active power in % of calculated power base value
Q REAL Reactive power
QPERCENT REAL Reactive power in % of calculated power base value
Section 6 1MRK 511 287-UUS A
Current protection
154
Technical manual