Name Type Description
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
TR_POS INTEGER Truck position indication
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
10.3.3.5 Settings
Table 181: SXCBR Non group settings (basic)
Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to move
after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate position
AdaptivePulse Not adaptive
Adaptive
- - Not adaptive Output resets when a new correct end position
is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
SuppressMidPos Disabled
Enabled
- - Enabled Mid-position is suppressed during the time
tIntermediate
10.3.4 Circuit switch SXSWI
10.3.4.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Circuit switch SXSWI - -
10.3.4.2 Functionality
The purpose of Circuit switch (SXSWI) function is to provide the actual status of positions
and to perform the control operations, that is, pass all the commands to primary
apparatuses in the form of disconnectors or grounding switches via binary output boards
and to supervise the switching operation and position.