Table 374: L4UFCNT Output signals
Name Type Description
ERROR BOOLEAN Error indication on counter limit and/or initial value
settings
OVERFLOW BOOLEAN Overflow indication on count of greater than MaxValue
LIMIT1 BOOLEAN Counted value is larger than or equal to CounterLimit1
LIMIT2 BOOLEAN Counted value is larger than or equal to CounterLimit2
LIMIT3 BOOLEAN Counted value is larger than or equal to CounterLimit3
LIMIT4 BOOLEAN Counted value is larger than or equal to CounterLimit4
VALUE INTEGER Counted value
12.3.6 Settings
Table 375: L4UFCNT Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
On
- - Disabled Operation Disable / Enable
CountType Set
Reset
DBLL or DLLB
-
- Set Select counting on positive and/or negative
sides
CounterLimit1 1 - 65535 - 1 100 Value of the first limit
CounterLimit2 1 - 65535 - 1 200 Value of the second limit
CounterLimit3 1 - 65535 - 1 300 Value of the third limit
CounterLimit4 1 - 65535 - 1 400 Value of the fourth limit
MaxValue 1 - 65535 - 1 500 Maximum count value
OnMaxValue Stop
Rollover Steady
Rollover Pulsed
-
- Stop Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
InitialValue
0 - 65535 - 1 0 Initial count value after reset of the function
12.3.7 Monitored data
Table 376: L4UFCNT Monitored data
Name
Type Values (Range) Unit Description
VALUE INTEGER - - Counted value
Section 12 1MRK 511 287-UUS A
Monitoring
456
Technical manual