10.3.5.5 Settings
Table 187: QCBAY Non group settings (basic)
Name
Values (Range) Unit Step Default Description
AllPSTOValid Priority
No priority
- - Priority Priority of originators
10.3.6 Local remote LOCREM
10.3.6.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local remote LOCREM - -
10.3.6.2 Functionality
The signals from the local HMI or from an external local/remote switch are applied via the
function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY function
block. A parameter in function block LOCREM is set to choose if the switch signals are
coming from the local HMI or from an external hardware switch connected via binary
inputs.
10.3.6.3 Function block
LOCREM
CTRLOFF
LOCCTRL
REMCTRL
LHMICTRL
OFF
LOCAL
REMOTE
VALID
IEC09000076_1_en.vsd
IEC09000076 V1 EN
Figure 113: LOCREM function block
10.3.6.4 Signals
Table 188: LOCREM Input signals
Name
Type Default Description
CTRLOFF BOOLEAN 0 Disable control
LOCCTRL BOOLEAN 0 Local in control
REMCTRL BOOLEAN 0 Remote in control
LHMICTRL INTEGER 0 LHMI control
1MRK 511 287-UUS A Section 10
Control
257
Technical manual