Name Type Description
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
TR_POS INTEGER Truck position indication
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
10.3.4.5 Settings
Table 184: SXSWI Non group settings (basic)
Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to move
after a command
tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate position
AdaptivePulse Not adaptive
Adaptive
- - Not adaptive Output resets when a new correct end position
is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
SwitchType Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
-
- Disconnector 1=LoadBreak,2=Disconnector,3=GroundSw,
4=HighSpeedGroundSw
SuppressMidPos Disabled
Enabled
- - Enabled Mid-position is suppressed during the time
tIntermediate
10.3.5 Bay control QCBAY
10.3.5.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Bay control QCBAY - -
1MRK 511 287-UUS A Section 10
Control
255
Technical manual