Name Type Description
I1RANG INTEGER I1Amplitude range
I1ANGL REAL I1 Angle
I2 REAL I2 Amplitude
I2RANG INTEGER I2 Magnitude range
I2ANGL REAL I2Angle
12.1.5.4 Settings
Table 354: CMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disable / Enable
3I0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
3I0Min 0 - 500000 A 1 0 Minimum value
3I0Max 0 - 500000 A 1 3300 Maximum value
3I0RepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is common
for all limits
3I0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I1Min 0 - 500000 A 1 0 Minimum value
I1Max 0 - 500000 A 1 1300 Maximum value
I1RepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
I1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I2Min 0 - 500000 A 1 0 Minimum value
I2Max 0 - 500000 A 1 1300 Maximum value
I2RepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is common
for all limits
I2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Section 12 1MRK 511 287-UUS A
Monitoring
432
Technical manual