Name of input Type Default Description Value when
activated
Value when
deactivated
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16)
are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to
an integer by the B16IFCVI function block.
11.7 Integer to boolean 16 conversion IB16A
11.7.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion IB16A - -
11.7.2 Functionality
Integer to boolean 16 conversion function IB16A is used to transform an integer into a set
of 16 binary (logical) signals.
1MRK 511 287-UUS A Section 11
Logic
407
Technical manual